INSTANTANEOUS AND FUNCTION RELAYS CSP
rear wiring socket with clips SRDL 4.8
rear wiring socket / PCB mounting SRC
front wiring socket with clips SVDL
front wiring socket with clips SPVDL
front wiring socket / screw terminals SVB
front wiring socket / screw terminals SPVB |
|
DESCRIPTION |
|
Impulse relay with fixed duration - 2 CO contacts - 6 A.
CSP relay is equipped in its standard version of : a locking system with elastic clips on the basis and clasps on the cover, two hexagonal withdrawal clasps permitting up to 36 possibilities (voltage, function) and a removable label-holder on front face.
Pluggable on the following sockets : SVB, SPVB, SVDL, SPVDL, SRDL 4,8 and SRC.
|
|
Dimensions |
|
Connection |
|
|
|
|
|
|
|
|
|
OPERATION PRINCIPLE |
|
Functions :
* ET : impulse on voltage application
* MT : impulse on voltage lack.
duration of impulse contact : 0,15 to 1 s
Interval between 2 operations : > 1 s
Contacts rating in DC :
* resistive load 0,5 A - 48 V : > 10.000.000 operations
* resistive load 0,5 A - 125 V : > 5.000.000 operations
* inductive load L/R 40 ms - 3A x 24 V or 1 A x 48 V or 4 A x 125 V : > 300.000 operations.
Contacts rating in AC :
* resistive load I = 6 A - 220 V : 500.000 operations
* inductive load I = 4A - cos phi 0,5 - 220 V > 500.000 operations. |
|
TECHNICAL FEATURES |
|
Function |
impulse (ET - MT) |
|
Presentation |
under cover |
|
Connection |
on front or rear wiring socket |
|
Number of mechanical operations |
20.000.000 |
|
Operating temperature |
- 10 to + 55°C |
|
Storage temperature |
- 40 to + 85°C |
|
Shock voltage |
3 KV (wave 1,2/50 µs) |
|
Dielectric strength |
2200 to 2500 V eff 50 Hz |
|
Insulation resistance |
C250 V (according to NFC 45-202 & VDE 0110) |
|
Weight |
180 g. |
|
Protection level |
IP 40 (according to NFC 20-010) |
|
Resistance to mechanical shocks |
severity 30 A (NFC 20-610 & CEI 682-25/Test Ea) |
|
Resistance to vibrations |
frequency range 10-55 Hz, 0,35 mm crest |
|
COIL DATA |
|
|
Direct current |
Alternative current |
|
Min. nominal voltage DC |
12 V |
12 V |
|
Min. nominal voltage AC |
220 V |
230 V |
|
Operating range |
-20/+10% of nominal voltage |
|
Power requirement |
ET : 2,5 W - MT : 0,5 W |
|
|
|
CONTACTS |
|
Number of contacts |
2 |
|
Max. load current |
6 A per contact |
|
Low power switching |
0,1 W with min voltage 6 V or I min 10 mA |
|
Response time |
ET < 20 ms - MT < 15 ms |
|
VERSIONS |
|
. CSP relay with specific voltages
. CSP relay with different impulse time.
Homologations & conformities :
NFC 45-250
CEI 255-1-00
|
Instantaneous relays 2 contacts / Model 1210Tec-Automatismes Model 1210 ınstantaneous relays, model 1210 2 contacts ınstantaneous relays 2 contacts,Instantaneous relays
2 contacts
1210 series
Instantaneous relay 2 or 3 CO contacts.
Pluggable on front wiring socket (9215) or rear wiring socket (9210) - 8 or 11 pins
INSTANTANEOUS AND FUNCTION RELAYS 2 contac / Model CSPImpulse relay with fixed duration - 2 CO contacts - 6 A.
CSP relay is equipped in its standard version of : a locking system with elastic clips on the basis and clasps on the cover, two hexagonal withdrawal clasps permitting up to 36 possibilities (voltage, function) and a removable label-holder on front face.
Pluggable on the following sockets : SVB, SPVB, SVDL, SPVDL, SRDL 4,8 and SRC.
Flashing relays 2 contacts / Model CSMMultifunction, multi-voltages, multirange timer relay - 2 timed contacts/2 instantaneous contacts - 3 A.
Pluggable on the following sockets : SVB, SPVB, SRC, SVDL, SPVDL and SRDL 4.8.
Instantaneous relays 2 contacts / Model CAQMTI Instantaneous relays 2 contacts / CAQ Instantaneous relay with rapid memory,
Pluggable on socket with a withdrawal clasp and square guide pins which can act as a key to ensure that the correct relay is used at the correct voltage
Flashing relays 2 contacts / Model CAPSabit süreli darbe rölesi. 1 dürtü temas ve 2 CO rehber.
Doğru röle doğru voltajda kullanılmasını sağlamak için bir anahtar olarak hareket edebilir bir geri çekilme toka ve kare kılavuz pimleri ile soket üzerinde Takılabilir ( bu sitenin teknik destek sayfalarında bizim çekilme kılavuzuna bakın )
aşağıdaki yuva üzerinde Takılabilir: EVB1 / CA, ERC1CA veya ERDL1CA.